BETA-LDG Stainless Steel Body Electromagnetic Fiowmeter
Magnetic flowmeters operate under the principle of Faraday's Law of Electromagnetic Induction to measure liquid velocity. Following Faraday's Law, magnetic flowmeters measure the velocity of conductive liquids in pipes, such as water, acids, caustic, and slurries. In order of usage, magnetic flowmeter use in water/wastewater industry, chemical, food and beverage, power, pulp and paper, metals and mining, and pharmaceutical application.




| Accuracy | ±0.5%,±2mm/s(flowrate<1m/s) |
| Electric conductivity | Water: Min. 20μS/cmOther liquid: Min. 5μS/cm |
| Flange | ANSI/JIS/DIN DN10…600 |
| Ingress protection | lP65 |
| Product | Electromagneticflowmeter |
| Model | BETA-LDG |
| Diameternominal | DN15~DN1000 |
| Nominalpressure | 0.6~4.0MPa |
| Accuracy | ±0.5%,±2mm/s(flowrate<1m/s) |
| Linermaterial | PFA,F46,Neoprene,PTFE,FEP |
| Electrodematerial | StainlesssteelSUS316, HastelloyC, Titanium,Tantalum Platinum-iridium |
| Mediumtemperature | Integraltype: -10℃~80℃ Splittype: -25℃~180℃ |
| AmbientTemperature | -10℃~60℃ |
| Electricalconductivity | Water20μS/cmothermedium5μS/cm |
| Structuretype | Tegraltype,splittype |
| Ingress protection | lP65 |
| Productstandard | JB/T9248-1999ElectormagneticFlowmeter |
Mag meter works based on Faraday's law, when the liquid goes through the pipe at the flow rate of v with a diameter D, within which a magnetic flux density of B is created by an exciting coil, the following electromotive E is generated in proportion to flow speed v:
E=K×B×V×D
Where:
E-Induced electromotive force
K-Meter constant
B-Magnetic induction density
V-Average flow speed in cross-section of measuring tube

Application
Electromagnetic flowmeters have been used throughout industries for more than 60 years.
These meters are applicable for all conductive liquids, such as: Domestic water, industrial water, raw water, ground water, urban sewage, industrial wastewater, the processed neutral pulp, pulp slurry, etc

Description


เรื่องน่าสนใจอื่น ๆ
-
BETACF-UT Series
BETACF-UT SeriesU-tubes Coriolis Mass Flowmeter (BETACF-UT)Item No.: 2 BETACF-UT.....
-
District ultrasonic heat meter
District ultrasonic heat meter District Ultrasonic Heat (Cooling) Meter (BETA-HN.....
-
District ultrasonic water meter
District ultrasonic Water meter (Bulk water meters) (BETA-W7)Item No.: 26.4BETA-.....
-
BETA-LWGY Turbine flowmeter thread connection
BETA-LWGY Turbine Flowmeter Thread ConnectionBETA-LWGY series liquid turbi.....
-
BETA-LUGB Vortex flowmeter without temperature
BETA-LUGB Vortex Flowmeter Without Temperature & Pressure Compensation .....
-
BETA-LUGB Vortex flowmeter with temperature & pressure compensation
BETA-LUGB Vortex Flowmeter With Temperature & Pressure CompnsationBETA-LUGB .....
-
BETA-LUGB Vortex flowmeter wafer installation
BETA-LUGB Vortex Flowmeter Wafer InstallationBETA-LUGB Vortex flowmeter work on .....
-
Magnetic flow transmitter
Magnetic Flow TransmitterElectromagnetic flow transmitter adopts LCD indicator a.....